13

Immediate Stop

Indramat · ServoDyn D Servo Drive

¿Qué significa 13 ?

This error occurs when the +24 Vdc signal is applied to the CLM01.3-M's Immediate Stop input (connector X3, pin 5). This input is designed to command an immediate halt to machine operation for safety purposes.

Causas comunes

  • The Immediate Stop pushbutton on the machine has been pressed, activating the input.
  • Faulty wiring or a short circuit is causing a continuous +24 Vdc signal to be present at connector X3, pin 5.
  • A malfunctioning Immediate Stop pushbutton is physically stuck or electrically shorted.
  • External control logic or device inadvertently activating the Immediate Stop input.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify that the Immediate Stop pushbutton is not currently pressed or stuck in an actuated position.

  2. 2

    Consult the machine builder's wiring diagrams to understand how the Immediate Stop input (X3, pin 5) is integrated into the flying cutoff system.

  3. 3

    Check the wiring at CLM01.3-M connector X3, pin 5 for any loose connections, shorts to +24 Vdc, or damage.

  4. 4

    Inspect the Immediate Stop pushbutton for mechanical damage or wear that could cause it to stick.

  5. 5

    If external control is involved, verify the output signal from the controlling device that feeds the Immediate Stop input.

Ver todos los códigos en este manual (51)