F8130

Firmware of option 2 of safety technology defective

Indramat · Indradrive

¿Qué significa F8130 ?

The firmware for the safety technology option module 2 is detected as defective or corrupted. Similar to F8129, this prevents safety functions from operating and results in drive shutdown for safety compliance.

Causas comunes

  • Corrupted firmware in safety option module 2.
  • Incorrect firmware version loaded for the specific safety option module.
  • Hardware defect within the safety option module 2.
  • Communication error with the safety option module.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Cycle power to the IndraDrive.

  2. 2

    Verify the correct firmware version for safety option module 2 is installed and re-flash it if necessary.

  3. 3

    Check the physical seating and connections of safety option module 2 within the IndraDrive.

  4. 4

    Ensure the safety configuration parameters are valid and consistent.

  5. 5

    If the error persists, the safety option module 2 itself may be defective and require replacement.