Traduciendo...
F4004

Error during phase progression

Indramat · Indradrive

¿Qué significa F4004 ?

The communication between the IndraDrive and its master controller failed to progress to the next expected communication phase. This indicates a stall or failure in advancing through the required communication states (e.g., from phase 0 to 1, or 1 to 2), preventing operational mode.

Causas comunes

  • Master controller not issuing the correct phase progression commands.
  • Drive not acknowledging phase change requests.
  • Communication bus issues (e.g., noise, cable damage) preventing reliable phase negotiation.
  • Incorrect communication parameters in either the master or slave.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify the configuration of the master controller to ensure it is correctly managing the communication phase progression.

  2. 2

    Inspect the communication cable and connections for any physical damage or loose contacts.

  3. 3

    Check for any errors or warnings on the master controller that might indicate communication issues.

  4. 4

    Review the IndraDrive's communication parameters (e.g., bus address, baud rate) to ensure they are correct.

  5. 5

    If applicable, use a bus analyzer tool to monitor communication traffic and identify the exact point of failure in phase progression.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas