F873

Power Supply Driver Stage Fault

Indramat · ECODRIVE Controller

¿Qué significa F873 ?

The voltage supply for the ECODRIVE DKC01.1/DKC11.1 drive's internal driver stage is monitored. If this voltage is detected as too low, the drive is turned off to prevent damage.

Causas comunes

  • Voltage supply of the driver stage is too low, indicating an internal fault within the drive controller.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify the incoming main AC supply voltage to the ECODRIVE DKC01.1/DKC11.1 drive controller is stable and within specified limits.

  2. 2

    Inspect for any external factors that might cause internal voltage drops, such as extreme ambient temperatures or blocked cooling vents.

  3. 3

    If external conditions are normal and the fault persists, it indicates an internal hardware fault; exchange the ECODRIVE DKC01.1/DKC11.1 drive controller.

Ver todos los códigos en este manual (24)