F262

Digital Output Overcurrent/Short Circuit

Indramat · ECODRIVE Controller

¿Qué significa F262 ?

This fault indicates that a digital output on the drive controller has exceeded its permissible current limit or experienced a short circuit. The drive triggers a shutdown to protect the output circuitry from damage. The specific current limit may vary depending on the output channel, with some outputs having a limit of 350mA and others 80mA.

Causas comunes

  • A short circuit present on one of the digital outputs.
  • The load connected to a digital output draws excessive current, exceeding its specified limit (e.g., > 350mA or > 80mA).

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Identify the specific digital output causing the fault.

  2. 2

    Disconnect the load from the affected digital output and measure the current draw of the load separately, ensuring it is within the specified limits (<350mA or <80mA).

  3. 3

    Check the wiring connected to the digital output for any short circuits to ground or to other potentials using a multimeter.

  4. 4

    Replace the faulty load device if it is drawing excessive current or has an internal short circuit.

Ver todos los códigos en este manual (24)