F220

Bleeder Overtemperature Shutdown

Indramat · ECODRIVE Controller

¿Qué significa F220 ?

The drive has detected that the regenerated energy from the machine's mechanism via the motor has exceeded the power capability of the bleeder resistor. To protect the bleeder from temperature damage, the drive will shut down according to the configured error reaction.

Causas comunes

  • The reflected energy from the machine’s mechanism over the motor is too large.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Reduce the acceleration value in the drive parameters to decrease the power regenerated during deceleration.

  2. 2

    Reduce the maximum velocity of the machine to decrease the kinetic energy that needs to be dissipated.

  3. 3

    Check the drive installation to ensure proper cooling and ventilation for the bleeder resistor.

  4. 4

    Evaluate if the application requires an additional or larger bleeder module to dissipate excess regenerative energy.