Motor Overtemperature Warning
Indramat · ECODRIVE Controller
¿Qué significa E251 ?
As soon as the motor temperature warning threshold (145°C) is exceeded, warning E251 is generated. The ECODRIVE DKC01.1/DKC11.1 drive continues to comply with the command value. A shutdown (F219) occurs only if the temperature error threshold (155°C) is exceeded.
Causas comunes
- The motor became overloaded; the effective torque required of the motor was above the allowable standstill continuous torque for too long.
- Poor ventilation around the motor, leading to insufficient cooling.
- Increased friction or mechanical binding in the driven load.
- Incorrect motor thermal model parameters in the ECODRIVE DKC01.1/DKC11.1 drive.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check the installation and loading of the motor. Verify if operating conditions have changed (e.g., increased friction, mechanical binding, poor ventilation).
- 2
Reduce the load on the motor or adjust the operating cycle to allow sufficient cooling time.
- 3
Verify the motor current against the motor nameplate FLA and the application requirements.
- 4
Inspect the motor temperature sensor wiring for continuity and correct connection to the ECODRIVE DKC01.1/DKC11.1 drive.