Traduciendo...
F384

Connection error at power supply unit

Indramat · CLM01.3-M Flying Cutoff Control

¿Qué significa F384 ?

With HVR power supply units only! This fault indicates that the power and control voltage connections are not in phase, specifically that terminals X5/U and X8/1, X5/V and X8/2, X5/W and X8/3 are conducting voltage to each other.

Causas comunes

  • Power and control voltage connections are incorrectly wired or in phase with each other.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    De-energize the Indramat HVR power supply unit and ensure all power is locked out according to safety procedures.

  2. 2

    Verify the wiring between the power input terminals (X5/U, X5/V, X5/W) and the control voltage input terminals (X8/1, X8/2, X8/3) for incorrect connections or cross-wiring.

  3. 3

    Using a multimeter in continuity or resistance mode, check for unintended electrical connections or short circuits between X5/U and X8/1, X5/V and X8/2, and X5/W and X8/3. There should be no continuity.

  4. 4

    Correct any incorrect wiring or short circuits identified between these terminal groups.

Ver todos los códigos en este manual (31)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Indramat CLM01.3-M Flying Cutoff Control