2082

Grid-tied/Off-grid Controller Abnormal

Huawei · SUN2000-(3KTL-10KTL)-M1 Solar Inverter

¿Qué significa 2082 ?

The inverter fails to communicate with the Smart Backup Box or an unrecoverable fault occurs on a circuit inside the Smart Backup Box. This impacts the inverter's ability to operate in grid-tied or off-grid modes.

Causas comunes

  • The inverter fails to communicate with the Smart Backup Box.
  • An unrecoverable fault occurs on a circuit inside the Smart Backup Box.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Send a shutdown command on the app. Turn off the AC output switch, DC input switch, and battery switch.

  2. 2

    Check whether the power cable and RS485 cable between the Smart Backup Box and the inverter are normal.

  3. 3