Traduciendo...
2062
Low insulation resistance
Huawei · SUN2000-(3KTL-10KTL)-M1 Solar Inverter
¿Qué significa 2062 ?
A short circuit exists between the PV array and the ground, or the PV array is in a moist environment with poor insulation. This is a critical safety fault indicating potential electrical leakage.
Causas comunes
- A short circuit exists between the PV array and the ground.
- The PV array is in a moist environment and the circuit is not well insulated to the ground.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check the impedance between the PV array output and the ground. If a short circuit occurs or the insulation is insufficient, rectify the fault.
- 2
Check whether the PE cable of the SUN2000 is correctly connected.
- 3
If the impedance is confirmed to be lower than the specified protection threshold in a cloudy or rainy environment, log in to the app, SmartLogger, or NMS and set the Insulation resistance protection threshold.
Datos técnicos verificados. Última actualización: March 2026
Fallas relacionadas
Fuente: Huawei SUN2000-(3KTL-10KTL)-M1 Solar Inverter