Grid relay is sticking or neutral conductor ground voltage too high
Fronius · Solar Energy
¿Qué significa 457 ?
The inverter is unable to feed energy into the grid due to either a sticking grid relay or an excessively high neutral conductor ground voltage. The neutral conductor ground voltage must be less than 30V for safe operation.
Causas comunes
- Malfunctioning (sticking) grid relay
- Neutral conductor ground voltage exceeding 30V
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check the grounding connection of the system
- 2
Measure the neutral conductor ground voltage and verify it is less than 30V
Datos técnicos verificados. Última actualización: March 2026