SRVO-023

Excessive Position Error at Stop

Fanuc · R-30iB Mate + Mate Plus Robot

¿Qué significa SRVO-023 ?

When the servo is commanded to stop, the actual position error is abnormally large. This can occur if the motor brake fails to release properly, or if there is a physical obstacle preventing the robot from maintaining its commanded stop position.

Causas comunes

  • Excessive position deviation from commanded path during motion hold.
  • Mechanical binding or external load exceeding servo torque capacity.
  • Incorrect servo tuning parameters (e.g., P gain, velocity gain).
  • Inaccurate encoder counts or resolution causing position discrepancies.
  • Motor encoder feedback signal noise or intermittent connection.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    If the brake is not released (check for absence of clack sound or vibration), check the continuity of the brake line in the robot connection cable and the mechanical unit cable.

  2. 2

    If no disconnection is found and the brake is still not released, replace the 6-Axis servo amplifier or the servo motor.

  3. 3

    If the brake is released, check whether an obstacle is disturbing the robot's motion.

Ver todos los códigos en este manual (53)