Energy Supply Stop (ECM)
Fanuc · Macro B CNC Programming
¿Qué significa U ?
The potential difference across the Energy Charge Module's (ECM) Capacitor Modules is detected to be more than 300V, indicating an unsafe high voltage condition. This suggests a failure in the charging or discharge control, or a dangerous energy imbalance within the module.
Causas comunes
- Interruption in the main energy supply to the ECM.
- Loss of DC bus voltage (e.g., below P24-2 threshold).
- Power supply unit failure.
- Circuit breaker tripped or blown fuse in the main power line.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Immediately stop the machine using the emergency stop button and open the external Main Circuit Contactor (MCC) of the Power supply.
- 2
Measure the voltage across the Capacitor Modules (A06B-6158-H020) to confirm it exceeds 300V.
- 3
Inspect the ECM Control Module (A06B-6158-H010) for proper regulation of charging and discharging operations.
- 4
Check the Resistor Module (A06B-6158-H030) and its connections to ensure it can properly dissipate energy when commanded or during an emergency stop.
- 5
Verify the main power supply and connected regenerative units for stable operation and correct voltage levels to prevent overcharging of the capacitor modules.