Resistor Module Abnormal Discharge (1) (ECM)

Fanuc · Macro B CNC Programming

¿Qué significa F ?

The Energy Charge Module's (ECM) Capacitor Modules are not discharging as expected, possibly due to a fault in the Resistor Module (A06B-6158-H030) or its control circuit. This indicates a failure in the controlled release of stored energy, which could lead to overvoltage.

Causas comunes

  • Resistor module (ECM) failure to discharge within expected timeframes.
  • Faulty discharge resistor element in the ECM.
  • Control signal issue for the discharge circuit (ECM).
  • Overload condition preventing proper discharge of the resistor module.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Immediately stop the machine using the emergency stop button and open the external Main Circuit Contactor (MCC) of the Power supply.

  2. 2

    Check the Resistor Module (A06B-6158-H030) for any visible damage, signs of overheating, or a blown fuse. Its expected resistance is 30 ohm (page 578).

  3. 3

    Inspect the wiring of the discharge circuit between the ECM Control Module (A06B-6158-H010) and the Resistor Module for breaks or loose connections.

  4. 4

    Verify the control signals that initiate discharge to the Resistor Module, ensuring they are correctly issued by the Control Module.

  5. 5

    If the alarm persists, the Resistor Module may be faulty and require replacement.

Ver todos los códigos en este manual (26)