Motor phase V missing
Danfoss · VLT Micro Drive FC 51
¿Qué significa 31 ?
One of the motor output phases (Phase V) is detected as missing by the drive. This typically indicates a disconnected motor cable, a broken wire, or a poor connection at either the drive or motor terminals, preventing proper motor operation.
Causas comunes
- Open circuit in the motor cable for phase V between the drive's V terminal and the motor's V terminal.
- Loose or corroded connection at the drive's output terminal V or the motor's terminal box for phase V.
- Internal failure of an output IGBT for phase V within the drive.
- Open circuit fault in the motor winding for phase V, resulting in no current path.
- Dislodged or damaged busbar connection for phase V inside the drive's power section.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
De-energize the drive and verify 0VDC at the drive's U, V, W output terminals.
- 2
Measure continuity of the motor cable for phase V from the drive's V terminal to the motor's V terminal.
- 3
Inspect connections at drive terminal V and the motor's terminal box for phase V for looseness, corrosion, or damage.
- 4
Measure resistance of the motor windings (U-V, V-W, W-U) at the motor's terminal box, verifying they are balanced and within specification (e.g., 0.5-20 Ohms).
- 5
If motor and cable are confirmed good, measure resistance between drive output terminal V and the DC bus (+) and (-) terminals to check for IGBT integrity.