Illegal data value (Modbus Exception)

Danfoss · VLT Micro Drive FC 51

¿Qué significa 3 ?

A value contained in the Modbus query data field is not an allowable value for the server (drive). This indicates a structural fault in the remainder of a complex request, such as an incorrect implied length. It does NOT mean a submitted data item is outside an application's expectation, as the Modbus protocol doesn't interpret specific register values.

Causas comunes

  • Attempting to write an out-of-range value to a specific Modbus register (e.g., motor speed limit above max RPM).
  • Writing an invalid data type to a Modbus register (e.g., attempting to write a string to a numeric parameter).
  • Modbus master sending a command to a read-only register with a write function code.
  • Drive operating mode preventing a specific parameter change (e.g., writing to P1-01 while drive is running).
  • Incorrect scaling factor applied by the Modbus master for a specific parameter (e.g., decimal values expected as integers).

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Review the Modbus communication log for the exact register address and data value being written at the time of the fault.

  2. 2

    Consult the drive's Modbus register map to confirm the valid data range, data type, and read/write permissions for the specified register.

  3. 3

    Ensure the Modbus master (e.g., PLC, HMI) is sending values within the specified limits and in the correct format (e.g., 0-100% for P1-02).

  4. 4

    Verify the drive's current operating status (e.g., idle, running) and if the target parameter (e.g., P0-10) can be modified in that state.

  5. 5

    Test writing a known valid value to the problematic Modbus register to isolate if the issue is with the value itself or the register access.

Ver todos los códigos en este manual (51)
Datos técnicos verificados. Última actualización: March 2026