Traduciendo...
ALARM 16

Short circuit

Danfoss · VLT HVAC Drive High Power

¿Qué significa ALARM 16 ?

There is a short circuit condition present in the motor or its wiring. This is a critical fault that can lead to immediate damage of the frequency converter's output stage if not quickly resolved.

Causas comunes

  • Motor phase-to-phase short circuit due to winding insulation breakdown.
  • Motor phase-to-ground short circuit from moisture ingress or insulation degradation.
  • Motor cable insulation failure between phases or to ground (e.g., due to chafing or mechanical damage).
  • Water or conductive debris in motor terminal box causing short circuit.
  • Faulty frequency converter output IGBT leading to a detected short circuit (less common).

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Disconnect main power supply to the frequency converter at the upstream breaker. Verify zero voltage at L1, L2, L3 terminals.

  2. 2

    Disconnect the motor cables (U, V, W) from the frequency converter output terminals (T1, T2, T3).

  3. 3

    Measure insulation resistance between motor phases (U-V, V-W, W-U) and from each phase to motor frame ground using a megohmmeter (500VDC).

  4. 4

    Measure continuity and insulation resistance of the motor cables from drive terminals to motor terminals.

  5. 5

    Visually inspect motor cables for signs of physical damage, chafing, or signs of overheating along their entire length.

  6. 6

    If motor or cable insulation resistance is below 1 Megohm, isolate and replace the faulty component.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Danfoss VLT HVAC Drive High Power