Short circuit
Danfoss · VLT HVAC Drive High Power
¿Qué significa ALARM 16 ?
There is a short circuit condition present in the motor or its wiring. This is a critical fault that can lead to immediate damage of the frequency converter's output stage if not quickly resolved.
Causas comunes
- Motor phase-to-phase short circuit due to winding insulation breakdown.
- Motor phase-to-ground short circuit from moisture ingress or insulation degradation.
- Motor cable insulation failure between phases or to ground (e.g., due to chafing or mechanical damage).
- Water or conductive debris in motor terminal box causing short circuit.
- Faulty frequency converter output IGBT leading to a detected short circuit (less common).
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Disconnect main power supply to the frequency converter at the upstream breaker. Verify zero voltage at L1, L2, L3 terminals.
- 2
Disconnect the motor cables (U, V, W) from the frequency converter output terminals (T1, T2, T3).
- 3
Measure insulation resistance between motor phases (U-V, V-W, W-U) and from each phase to motor frame ground using a megohmmeter (500VDC).
- 4
Measure continuity and insulation resistance of the motor cables from drive terminals to motor terminals.
- 5
Visually inspect motor cables for signs of physical damage, chafing, or signs of overheating along their entire length.
- 6
If motor or cable insulation resistance is below 1 Megohm, isolate and replace the faulty component.