Traduciendo...
38

Internal fault (General)

Danfoss · VLT HVAC Drive FC 102

¿Qué significa 38 ?

A general internal fault has been detected within the frequency converter, preventing normal operation. A specific sub-code, referenced in Table 7.6, provides more detailed diagnostic information about the nature of the internal issue. This fault indicates a critical hardware or software problem requiring specific troubleshooting based on the sub-code.

Causas comunes

  • Transient hardware malfunction on the control board or power card due to EMI or power fluctuation.
  • A general firmware error or corruption that prevents normal drive operation.
  • Internal component failure (e.g., processor, memory) not specifically covered by other sub-codes.
  • Insufficient or unstable internal DC bus voltage due to auxiliary power supply issues.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Cycle power to the frequency converter (off for 1 minute, then on) to reset the internal logic.

  2. 2

    2. Check the LCP display for any specific sub-code (e.g., "38.X") that provides more detailed diagnostic information.

  3. 3

    3. Perform a parameter initialization (P14-22 set to '2') to rule out parameter corruption, then reload known good settings.

  4. 4

    4. Ensure stable input power and verify proper grounding to prevent EMI related issues.

Ver todos los códigos en este manual (75)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Danfoss VLT HVAC Drive FC 102