Inverter overload
Danfoss · VLT AutomationDrive FC 301/302
¿Qué significa 9 ?
The frequency converter has been operating at more than 100% overload for an excessive period and is about to trip. A warning is issued at 98% overload, and a trip (alarm) occurs at 100%. The frequency converter cannot be reset until the internal thermal counter drops below 90%.
Causas comunes
- Motor operating at continuous current above its rated value due to sustained mechanical overload (e.g., clogged pump, seized bearing).
- Incorrect motor parameters programmed in the drive (e.g., P1-20 Motor Rated Current, P1-23 Motor Rated Power are too low).
- Motor size is too small for the application's required load, leading to continuous high current draw.
- Motor output cable impedance too high or cable length excessive, causing increased current draw for a given load.
- Drive cooling fan failure leading to insufficient cooling and subsequent derating of overload capacity.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Measure the actual motor current (e.g., with clamp meter on U, V, or W output phases) and compare to motor nameplate and P1-20.
- 2
Verify the motor's mechanical load by manually turning the shaft (if possible) for unusual resistance or friction.
- 3
Cross-check all motor parameters in the drive (e.g., P1-20 to P1-25) against the motor nameplate data.
- 4
Inspect the drive's internal and external cooling fans for proper operation and ensure unobstructed air circulation.
- 5
Increase the drive's acceleration and deceleration ramp times (P3-41, P3-42) to reduce peak currents during transients.
- 6
Consider upsizing the motor or drive if continuous current remains above 95% of rated current under normal load.