No motor

Danfoss · VLT AutomationDrive FC 301/302

¿Qué significa 3 ?

No motor is connected to the output of the frequency converter. This indicates an open circuit condition on the motor output terminals.

Causas comunes

  • Motor cable severed or disconnected from the drive output terminals (U, V, W) or the motor terminal box.
  • Internal open circuit in one or more motor windings (e.g., due to thermal overload, insulation breakdown).
  • Loose or corroded electrical connections on the motor terminal block or the drive's output terminals.
  • External motor protection device (e.g., thermal overload relay, contactor) tripped or faulty, interrupting power.
  • Incorrect motor cable sizing or severe cable damage causing high resistance or an open circuit.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Safely de-energize the drive and motor. Verify all physical connections from the drive output (U, V, W) to the motor terminal box.

  2. 2

    Measure the resistance between each pair of motor output terminals at the drive (U-V, V-W, W-U); all should be equal and low impedance (e.g., <1 Ohm).

  3. 3

    Measure the insulation resistance of the motor windings to ground using a megohmmeter (e.g., 500VDC test, expected >1MOhm).

  4. 4

    Disconnect the motor cables from the motor terminal box and measure the resistance of each motor winding (U-V, V-W, W-U) directly at the motor.

  5. 5

    Inspect any motor contactor or starter (if present) for proper operation, ensuring all main contacts close when commanded.

Ver todos los códigos en este manual (66)
Datos técnicos verificados. Última actualización: March 2026