Torque limit exceeded
Danfoss · VLT AutomationDrive FC 301/302
¿Qué significa 12 ?
The motor or generator torque has exceeded the configured limit defined in parameter 4-16 Torque Limit Motor Mode or parameter 4-17 Torque Limit Generator Mode. Parameter 14-25 Trip Delay at Torque Limit can elevate this condition from a warning to an alarm after a set delay.
Causas comunes
- Sudden increase in load or mechanical obstruction causing the motor to demand torque beyond configured limits (e.g., P4-16, P4-17).
- Rapid acceleration or deceleration demand exceeding the drive's and motor's torque capabilities for the set ramp times.
- Incorrectly set torque limits (e.g., P4-16 Torque Limit Motor Mode) that are too restrictive for the application's actual demands.
- Feedback sensor (e.g., encoder) issue leading to inaccurate speed or position data, causing the control loop to command excessive torque.
- Motor parameter misconfiguration (e.g., P1-20, P1-21) leading to incorrect torque estimation by the drive.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Review parameter 4-16 (Torque Limit Motor Mode) and 4-17 (Torque Limit Generator Mode) settings against application requirements and motor capabilities.
- 2
Monitor instantaneous motor torque (e.g., P16-24) during operation to identify when the limit is exceeded.
- 3
Inspect the mechanical load for binding, obstructions, or sudden changes in friction that would demand high torque.
- 4
Increase acceleration and deceleration ramp times (e.g., P3-41, P3-42) to reduce instantaneous torque demands.
- 5
If operating in closed loop, verify encoder feedback integrity (e.g., signal level, proper counts) using drive diagnostics (P16-52).