F2860
Overcurrent in mains-side power section
Bosch Rexroth · IndraDrive Troubleshooting
¿Qué significa F2860 ?
The current in the power transistor bridge has exceeded the maximum allowed device peak current. This results in the immediate de-energization of the drive, causing the motor to coast to a stop. The power supply is switched off due to this excessive current condition.
Causas comunes
- Short circuit in motor or motor cable.
- Device defective.
- Current loop parameterized differently (not for HMV01.1R), i.e., parameters do not match motor datasheet.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check motor cable and motor for short circuits.
- 2
Replace the device.
- 3
Check current loop parameters to see whether they differ from the parameters on the motor data sheet; correct them if necessary.