Incorrect direction of motion
Bosch Rexroth · IndraDrive MPx02
¿Qué significa F7031 ?
This safety technology error indicates that the IndraDrive MPx02 has detected motion in an incorrect or unintended direction, violating a safety-related directional monitoring function. This could be due to a control error or external influence, leading to an immediate safety stop.
Causas comunes
- Incorrect parameterization of safety-related direction monitoring (e.g., S-0-0102 'Safe direction').
- Programming error in the motion controller causing a command for the wrong direction.
- Motor phase reversal or encoder wiring issue, causing actual motion to be opposite of commanded.
- Mechanical system defect (e.g., backlash, broken gear) leading to unintended direction of movement.
- Encoder fault providing inverted or incorrect direction feedback.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Review and adjust the safety-related direction monitoring parameter (e.g., S-0-0102) in the IndraDrive MPx02 to ensure it aligns with the intended safe directions of motion.
- 2
Verify the motion program in the master controller or PLC, ensuring correct direction commands are issued.
- 3
Check the motor phasing and encoder wiring for correct connections. If necessary, reverse motor phases (U, V, W) or encoder direction parameter (S-0-0130 'Encoder direction of rotation').
- 4
Inspect the mechanical system for excessive backlash, loose couplings, or other defects that could cause unintended reversal.
- 5
Verify the motor encoder for correct direction sensing, checking for potential noise or signal issues.