F2836

DC bus balancing monitor error

Bosch Rexroth · IndraDrive MPx02

¿Qué significa F2836 ?

An error has been detected by the DC bus balancing monitor. This system ensures that the voltage across series-connected DC bus capacitors remains balanced. An imbalance can indicate a faulty capacitor, a problem with the balancing resistors, or an issue with the monitoring circuit itself, potentially leading to capacitor overvoltage and failure.

Causas comunes

  • Defective DC bus capacitor (e.g., increased ESR)
  • Faulty balancing resistors across DC bus capacitors
  • Problem with the DC bus voltage measurement circuitry
  • Interference affecting the balancing monitor's readings
  • Internal hardware fault in the balancing circuit

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify drive parameters related to DC bus configuration and monitoring via the IndraDrive HMI or software.

  2. 2

    Measure incoming AC supply phase-to-phase and phase-to-ground voltages at the drive input terminals to confirm stability, balance, and adherence to specifications.

  3. 3

    Inspect all external DC bus connections (if applicable in multi-axis setups or with external braking units) for proper seating, torque, and signs of damage or corrosion.

  4. 4

    Monitor the overall DC bus voltage and current values using the drive's diagnostic interface to observe for instability or deviations from expected levels under various load conditions.