F2260

Command current limit shutoff

Bosch Rexroth · IndraDrive MPx02

¿Qué significa F2260 ?

The drive has triggered a shutoff due to the command current exceeding its defined limit. This indicates that the control system demanded more current than the drive's safety or operational parameters allow, often to achieve a desired torque or acceleration. This can protect the motor and drive from overstress.

Causas comunes

  • Motor trying to accelerate too quickly
  • High mechanical load on the motor
  • Incorrect motor parameters (e.g., nominal current) in the drive configuration
  • Torque limits set too low in parameters
  • Mechanical binding or obstruction in the driven system

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify drive parameters such as peak current limits (e.g., S-0-0092), continuous current limits (S-0-0093), acceleration ramps (S-0-0052), and torque limits (P-0-0100) are correctly configured for the application and motor.

  2. 2

    Inspect the mechanical system for any obstructions, increased friction, binding, or excessive load that would require higher torque and current demand.

  3. 3

    Verify the configured motor data in the IndraDrive MPx02 (e.g., rated current, motor type, nominal speed) matches the actual motor nameplate specifications.

  4. 4

    Check motor power cabling for proper connections, insulation integrity, and continuity of all phases, and verify motor feedback (encoder) signal integrity and connection.