Traduciendo...
F2190

Incorrect Ethernet configuration

Bosch Rexroth · IndraDrive MPx02

¿Qué significa F2190 ?

The Ethernet network configuration of the drive is incorrect or incompatible. This fault indicates that the drive cannot properly establish or maintain communication over its Ethernet interface, affecting control, monitoring, and data exchange with other network devices. This will prevent network-based operation.

Causas comunes

  • Incorrect IP address, subnet mask, or gateway settings
  • Duplicate IP address on the network
  • Mismatch in Ethernet protocol settings (e.g., EtherCAT, PROFINET)
  • Faulty Ethernet cable or connection
  • Network switch configuration issues

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Inspect the Ethernet cable connecting the IndraDrive MPx02 to the network switch or controller for damage, proper seating, and correct cabling type.

  2. 2

    Check the status LEDs on the drive's Ethernet port and the corresponding port on the network switch for link activity and data transfer indications.

  3. 3

    Verify the drive's Ethernet network parameters (IP address, Subnet Mask, Gateway, device name/ID) in the IndraWorks software or drive HMI against the system's network design specifications.

  4. 4

    Verify the corresponding Ethernet network configuration (e.g., IP address of the drive in the PLC's hardware configuration) on the primary controller (PLC/NC) to ensure it matches the drive's settings.

  5. 5

    Check network reachability by attempting to ping the drive's assigned IP address from a connected computer or the network controller.

Ver todos los códigos en este manual (99)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Bosch Rexroth IndraDrive MPx02