F2018

Device overtemperature shutdown

Bosch Rexroth · IndraDrive C Drive Controllers

¿Qué significa F2018 ?

The drive controller or associated power electronics have reached a critical internal temperature, triggering a safety shutdown to prevent damage. This is a severe thermal event.

Causas comunes

  • Inadequate cooling for the drive due to blocked vents, fan failure, or high ambient temperature.
  • Sustained operation at or above the drive's rated output current.
  • Internal thermal sensor malfunction or incorrect reading.
  • Failure of internal cooling components.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Allow the drive controller to cool down completely before attempting to reset the fault.

  2. 2

    Check the drive's cooling fan for proper operation. Verify airflow direction and ensure no obstructions in the heatsink or ventilation openings.

  3. 3

    Measure the ambient temperature around the drive and ensure it is within the specified operating range.

  4. 4

    Reduce the load on the drive if possible, or verify that the drive is correctly sized for the application's continuous and peak current requirements.

Ver todos los códigos en este manual (66)