E2818
Phase failure
Bosch Rexroth · IndraDrive C Drive Controllers
¿Qué significa E2818 ?
One or more phases of the incoming AC mains power supply are missing or significantly unbalanced. This can cause severe operational issues and damage to the drive.
Causas comunes
- Loss of one or more phases in the incoming AC mains supply.
- Blown fuse or tripped circuit breaker in one phase.
- Loose or open connection in the mains power cabling.
- Faulty contactor or circuit breaker.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check all three phases of the incoming AC mains voltage (L1-L2, L2-L3, L3-L1) for balance and presence.
- 2
Inspect all fuses and circuit breakers in the mains power circuit and replace any blown fuses or reset tripped breakers.
- 3
Verify all power connections from the mains supply to the drive for tightness and continuity.
- 4
Check the functionality of any upstream contactors or phase monitoring relays.