E2816
Undervoltage in power section
Bosch Rexroth · IndraDrive C Drive Controllers
¿Qué significa E2816 ?
The DC bus voltage in the drive's power section has dropped below the minimum acceptable threshold. This indicates insufficient power available for motor operation.
Causas comunes
- Insufficient incoming AC mains voltage (see E2814).
- Excessive load causing a momentary drop in DC bus voltage.
- Faulty rectifier stage or pre-charge circuit in the drive.
- Internal power supply issue within the drive.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Measure the incoming AC mains voltage at the drive's input terminals and ensure it is stable and within specified limits.
- 2
Check the DC bus voltage at the +UDC/-UDC terminals on the drive during operation and ensure it remains above the undervoltage threshold.
- 3
Verify that the drive is correctly sized for the motor and application load, avoiding momentary overloads.
- 4
Inspect the pre-charge resistors and contactors/relays for proper functionality if the fault occurs during power-up.
Datos técnicos verificados. Última actualización: March 2026