E2814

Undervoltage in mains

Bosch Rexroth · IndraDrive C Drive Controllers

¿Qué significa E2814 ?

The incoming AC mains voltage is below the acceptable operating threshold for the drive's power section. This can lead to insufficient DC bus voltage and operational issues.

Causas comunes

  • Incoming AC supply voltage sag or brownout.
  • Incorrect mains voltage setting in drive parameters for the actual supply.
  • Loose or high-resistance connections in the mains power circuit.
  • Overloaded mains supply causing voltage drop.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Measure the incoming AC mains voltage at the drive's input terminals and verify it is within the drive's specified operating range.

  2. 2

    Check all connections in the mains power circuit, including circuit breakers, contactors, and terminal blocks, for tightness and corrosion.

  3. 3

    Verify the mains voltage parameter setting in the drive configuration matches the actual incoming supply voltage.

  4. 4

    Monitor the mains voltage over time to detect transient sags or brownouts, especially during peak load conditions.