Traduciendo...
Diag 2 Flash 5

Field Voltage Too Low

Beckhoff · EL2904 TwinSAFE Fail-Safe Output Terminal

¿Qué significa Diag 2 Flash 5 ?

The voltage supplied to the power contacts of the terminal is below the permissible operating range (24V -15%/+20%). This can be caused by the voltage not being switched on, being switched on after the terminal supply, being generally too low, or by a short-circuit at an output causing a voltage drop. This affects the overall operation of the terminal's outputs and can lead to unreliable behavior or shutdown of safety functions.

Causas comunes

  • Degraded or undersized 24VDC power supply unit (PSU) failing under load, resulting in output voltage below 20.4VDC.
  • Excessive voltage drop across long field power wiring or undersized conductors, causing terminal voltage to fall below 20.4VDC.
  • Tripped circuit breaker or blown fuse on the 24VDC field power supply circuit.
  • Faulty power contact terminal block or connection issue preventing full voltage delivery to the module.
  • Incorrectly configured power-on sequence where the field voltage is not applied before the terminal initialization.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Using a calibrated multimeter, measure the 24VDC field supply voltage directly at the input terminals of the affected module. Voltage must be within 20.4VDC to 28.8VDC.

  2. 2

    2. Measure the output voltage of the 24VDC power supply unit (PSU) at its terminals. If it's consistently below 20.4VDC under normal load, replace the PSU.

  3. 3

    3. Inspect and verify the continuity of the fuse or integrity of the circuit breaker protecting the 24VDC field supply circuit. Replace fuse if open or reset breaker.

  4. 4

    4. Calculate the voltage drop for the field power wiring based on wire gauge and length; if excessive, install larger gauge wire or a localized power supply.

  5. 5

    5. Verify that the field power is enabled and stable for at least 500ms before the control system attempts to initialize the terminal to prevent startup race conditions.

Ver todos los códigos en este manual (11)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Beckhoff EL2904 TwinSAFE Fail-Safe Output Terminal