78

Flux Amps Reference Range

Allen-Bradley · PowerFlex 700

¿Qué significa 78 ?

The value for flux amps determined by the Autotune procedure exceeds the programmed [Motor NP FLA] parameter. This indicates a discrepancy between the motor's actual flux current characteristics and the configured nameplate full load amperage, possibly due to incorrect motor data entry or an improperly sized motor.

Causas comunes

  • Calculated flux current reference is outside acceptable limits.
  • Motor model parameters (e.g., P2-xx) are incorrect.
  • Stator resistance estimation failure.
  • Low motor terminal voltage during operation.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Reprogram [Motor NP FLA] parameter with the correct motor nameplate Full Load Amperage value.

  2. 2

    Repeat the Autotune procedure.

Ver todos los códigos en este manual (49)
Datos técnicos verificados. Última actualización: March 2026