Traduciendo...
70
Power Unit Fault
Allen-Bradley · PowerFlex 700
¿Qué significa 70 ?
One or more of the output transistors were operating in the active region instead of desaturation. This can be caused by excessive transistor current or insufficient base drive voltage, indicating a failure within the drive's output power stage.
Causas comunes
- Malfunction within the power conversion or regulation stage.
- Overload condition exceeding the power unit's capacity.
- Internal component failure in the power stage.
- Inadequate cooling of the power unit.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check for damaged output transistors (e.g., using a multimeter for short circuits).
- 2
Replace the drive unit.
Datos técnicos verificados. Última actualización: March 2026
Fallas relacionadas
Fuente: Allen-Bradley PowerFlex 700