UnderVoltage
Allen-Bradley · PowerFlex 700
¿Qué significa 4 ?
The DC bus voltage has fallen below the minimum threshold (407V DC for 400/480V input, or 204V DC for 200/240V input). This fault indicates an insufficient incoming AC line voltage or a momentary power interruption. This condition can be enabled or disabled via [Fault Config 1] (page 1-46) based on application needs.
Causas comunes
- Input AC voltage to the drive is below the minimum operational threshold.
- Loss of one or more phases in the incoming power supply.
- Incorrect voltage setting for the drive (P0-01).
- Faulty DC bus capacitor or rectifier stage.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Monitor the incoming AC line voltage at the drive's input terminals for sags, drops, or power interruptions.
- 2
Verify parameter [Fault Config 1] on page 1-46 to ensure the undervoltage fault is configured as desired for the application.
Datos técnicos verificados. Última actualización: March 2026