24

Decel Inhibit

Allen-Bradley · PowerFlex 700

¿Qué significa 24 ?

The drive is not following a commanded deceleration because it is attempting to limit bus voltage. This indicates the DC bus voltage is rising due to regenerative energy, potentially exceeding safe limits and causing the drive to inhibit deceleration.

Causas comunes

  • External signal preventing deceleration (e.g., motor brake active).
  • Internal logic error during deceleration command.
  • Deceleration ramp time set too short for the load.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify input voltage is within the drive's specified limits.

  2. 2

    Verify system ground impedance follows proper grounding techniques.

  3. 3

    Disable bus regulation and/or add a dynamic brake resistor and/or extend the deceleration time parameter.