Traduciendo...
F073

EN Net Loss

Allen-Bradley · PowerFlex 520-series Adjustable Frequency

¿Qué significa F073 ?

Control through the drive's embedded EtherNet/IP adapter has been interrupted. This signifies a loss of communication between the drive and its EtherNet/IP master controller or PLC, resulting in the loss of remote command and control capabilities and potentially triggering a fault or shutdown.

Causas comunes

  • Broken or disconnected Ethernet cable between the drive's embedded EtherNet/IP port (RJ45) and the network switch/PLC.
  • Failure of the EtherNet/IP master controller (e.g., PLC CPU fault, communications module failure).
  • Incorrect IP address (Parameter P9-29), subnet mask (P9-30), or gateway (P9-31) configuration on the drive or the network.
  • Network switch failure, port lockout, or power loss to network infrastructure components.
  • Severe network congestion, broadcast storms, or duplicate IP addresses on the network, causing communication disruption.
  • Drive's embedded EtherNet/IP adapter hardware failure.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify the Ethernet cable connection to the drive's embedded EtherNet/IP port (RJ45) and the network switch/PLC is secure and undamaged.

  2. 2

    Check the link/activity LEDs on the drive's Ethernet port and the connected network switch port; they should indicate link presence and activity.

  3. 3

    Confirm the EtherNet/IP master controller (PLC) is running and configured to communicate with the drive; check PLC I/O tree and diagnostics.

  4. 4

    Verify the drive's IP address (P9-29), Subnet Mask (P9-30), and Gateway (P9-31) settings match the network topology using DriveTools SP or HMI.

  5. 5

    Ping the drive's IP address from a computer on the same subnet to confirm network layer connectivity.

  6. 6

    If the problem persists and network connectivity is confirmed, consider performing a firmware update or, if hardware failure is suspected, drive replacement.

Ver todos los códigos en este manual (48)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Allen-Bradley PowerFlex 520-series Adjustable Frequency