Traduciendo...
5
Jog Error
Allen-Bradley · MicroLogix 1400 Programmable Controllers
¿Qué significa 5 ?
The PTOX is in the idle state, and two or more of the following bits are simultaneously set: Enable (EN) bit, Jog Pulse (JP) bit, and Jog Continuous (JC) bit. This indicates conflicting jog commands. This error does not fault the controller and automatically clears when the error condition is removed.
Causas comunes
- Simultaneous activation of multiple jog-related control bits (EN, JP, JC) while the PTOX is idle.
- Incorrect control logic causing conflicting jog commands to be active at the same time.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Review the program logic to ensure that only one jog command (Jog Pulse or Jog Continuous) is active at a time.
- 2
Verify that the Enable (EN), Jog Pulse (JP), and Jog Continuous (JC) bits are not unintentionally set together while the PTOX is in an idle state.
- 3
Clear the conflicting bits in the control logic to resolve the error condition.
Datos técnicos verificados. Última actualización: March 2026
Fallas relacionadas
Fuente: Allen-Bradley MicroLogix 1400 Programmable Controllers