Recoverable Module Fault or Connection Timeout
Allen-Bradley · Compact 5000 I/O Analog Modules
¿Qué significa ModuleStatus:FlashingRed ?
The Module Status indicator is flashing red, which can signify several conditions: a module firmware update is in progress or failed, the device has experienced a recoverable fault, or a connection to the module has timed out. The specific cause needs to be determined via software diagnostics.
Causas comunes
- Module firmware update is in progress
- Module firmware update attempt failed
- Device experienced a recoverable internal fault
- Connection to the module has timed out (e.g., due to cable failure)
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Allow any module firmware update to progress to completion.
- 2
If a firmware update failed, re-attempt the firmware update procedure.
- 3
Use the Logix Designer application to access the module's configuration (Connection and Module Info categories) to determine the specific fault type.
- 4
To clear a recoverable fault, cycle power to the module (power off, then on).
- 5
To clear a recoverable fault, click 'Reset Module' in the Logix Designer application via the Module Info category of the Module Properties dialog box.
- 6
Use the Logix Designer application to check the Connection category in Module Properties for connection timeout status and determine the cause (e.g., inspect Ethernet cable integrity).