Traduciendo...
I.Chxx.Fault

Channel Data Inaccurate / Untrusted

Allen-Bradley · Compact 5000 I/O Analog Modules

¿Qué significa I.Chxx.Fault ?

This input tag, when set to 1, indicates that the data reported by channel xx is inaccurate and should not be used for control applications. This signifies a fundamental issue with data integrity for that specific channel, requiring immediate troubleshooting of the channel's setup and connections. The tag automatically resets to 0 once the underlying condition is removed.

Causas comunes

  • The specific channel (xx) is disabled in the module configuration.
  • An Open Wire condition exists on the input module.
  • A No Load condition exists on the output module.
  • An Underrange or Overrange condition is present on the input or output signal.
  • A Short Circuit condition is detected on an output channel.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify that channel xx is enabled in the module's Logix Designer application configuration.

  2. 2

    Physically inspect the wiring for channel xx for open circuits or disconnections.

  3. 3

    For output channels, verify the load is properly connected and functioning.

  4. 4

    Measure the input or output signal at channel xx to confirm it is within its specified operating range.

  5. 5

    For output channels, measure output current to check for short circuit conditions.

Ver todos los códigos en este manual (33)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Allen-Bradley Compact 5000 I/O Analog Modules