Traduciendo...
Group Indicator Flashing Red

Faults Present in Undisplayed Group Channels

Allen-Bradley · Compact 5000 Digital I/O Modules

¿Qué significa Group Indicator Flashing Red ?

The Group A or Group B indicator is flashing red, signifying that I/O status is NOT currently displayed for this group of channels, but at least one fault exists on channels within this group. This serves as an alert that a fault is present in a non-active channel group.

Causas comunes

  • One or more individual I/O channels within the non-displayed group (Group A or Group B) have an active fault condition.
  • The Group A or Group B button has not been pressed to display the status for the faulted group.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Press the physical Group A or Group B button on the module faceplate to switch the display to the faulted group of channels.

  2. 2

    Examine the individual channel I/O status indicators (if available on the module faceplate) for specific fault indications once the group is displayed.

  3. 3

    Access the module's diagnostic information in Studio 5000 Logix Designer to pinpoint the specific channel faults within the group.

Ver todos los códigos en este manual (38)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas