FF56

MOTOR PHASE

ABB · ACS800

¿Qué significa FF56 ?

One of the motor phases has been lost, causing an imbalance in the motor current. This can be due to a fault in the motor, motor cable, external thermal relay, or an internal drive issue. This protection is linked to programmable Fault Function 30.16.

Causas comunes

  • An open circuit or high resistance connection in one of the motor phases (U, V, or W) due to a cable fault or loose terminal.
  • Internal winding fault (e.g., open circuit) within the motor.
  • A tripped or faulty external thermal relay in the motor circuit, if used.
  • An internal fault within the ACS800 drive's output stage.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Check motor windings and motor cables for open circuits or high resistance using a multimeter (ohmmeter).

  2. 2

    Verify all motor cable connections are secure and tightened to specification at both the drive output terminals and the motor terminals.

  3. 3

    Inspect and test the thermal relay (if used) for proper operation and correct wiring; ensure its contacts are clean and making good connection.

  4. 4

    Check parameter 30.16 (MOTOR PHASE LOSS) setting. If protection is temporarily not desired (e.g., during specific test cases), consider disabling it with caution and appropriate safety measures.

Ver todos los códigos en este manual (33)