7112

BR OVERHEAT

ABB · ACS800

¿Qué significa 7112 ?

The brake resistor connected to the ABB ACS800 drive is experiencing an overload condition, leading to excessive temperature. This fault (3.17 FW 5 bit 3) can reduce braking effectiveness, potentially damage the resistor or associated components, and indicates that the braking duty cycle may be too demanding or improperly configured.

Causas comunes

  • Brake resistor overload due to an excessive braking duty cycle for the application.
  • Incorrect parameter settings for the brake chopper or resistor overload protection in parameter group 27 BRAKE CHOPPER.
  • The braking cycle demands exceed the allowed limits for the installed brake resistor's thermal capacity.
  • Excessive AC supply voltage to the drive can affect regenerative braking behavior.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Stop the ABB ACS800 drive and allow the brake resistor to cool down to a safe operating temperature before resuming operation.

  2. 2

    Review and adjust parameter settings in group 27 BRAKE CHOPPER to ensure they match the installed brake resistor's specifications and the application's braking requirements.

  3. 3

    Evaluate the braking duty cycle of the application; ensure it meets the specifications of the brake resistor. Reduce braking demands or consider a larger resistor if consistently hitting limits.

  4. 4

    Measure the drive's AC supply voltage to confirm it is within specified limits and not excessively high, which can impact regenerative voltage levels.

  5. 5

    Inspect the brake resistor for any visible signs of physical damage, such as burnt areas, cracks, or discolored components.