80B1

Signal supervision 2

ABB · ACS880

¿Qué significa 80B1 ?

A fault generated by the signal supervision 2 function, indicating that a monitored signal has violated its defined limits or conditions. This signifies an abnormal condition in a specific process signal that the drive is supervising. Unresolved, it can lead to incorrect operation or safety issues.

Causas comunes

  • Monitored process sensor (e.g., pressure, flow) providing an out-of-range signal value (e.g., analog input AI1 < 4mA or > 20mA).
  • Breakage or short circuit in the sensor wiring for the monitored signal (e.g., between sensor and drive terminal X1:AI1).
  • Incorrectly configured signal limits or scaling parameters (e.g., P3-10 min/max for analog input) for the supervision function.
  • External electrical noise or ground loop affecting the low-voltage analog signal input, causing erratic readings.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Measure the voltage or current output directly from the process sensor with a multimeter to verify its actual value (e.g., 4-20mA loop).

  2. 2

    2. Inspect and continuity-test the signal cabling between the sensor and the drive's analog input terminals (e.g., X1:AI1).

  3. 3

    3. Review the signal supervision parameters (e.g., P3-11 'Signal min limit', P3-12 'Signal max limit') and adjust them to match the expected operating range.

  4. 4

    4. Verify proper shielding and grounding of the analog signal cable, ensuring shield is connected at one end (e.g., drive end) to minimize noise.

  5. 5

    5. Test the sensor's own power supply voltage (e.g., 24VDC at sensor terminals) to ensure it is within specified limits.

Ver todos los códigos en este manual (116)
Datos técnicos verificados. Última actualización: March 2026