73B0

Emergency ramp failed

ABB · ACS880

¿Qué significa 73B0 ?

The motor has not stopped within the maximum allowed time after an emergency stop command (Off1 or Off3 mode) was issued. This indicates a failure in the emergency braking sequence, which could lead to unsafe operation if the system cannot stop as expected. The drive trips and coasts to a stop.

Causas comunes

  • Mechanical binding or excessive load on the motor shaft preventing it from decelerating within the programmed time.
  • Motor brake not engaging or failing to provide sufficient torque to stop the motor quickly (e.g., brake pads worn, spring fatigued).
  • Deceleration time parameter (e.g., P2-11 'Deceleration time 1') is set too long for the required emergency stop duration.
  • Motor current or torque limits (e.g., P1-54 'Motor current limit') are set too low, preventing sufficient braking torque during deceleration.
  • Failure of the drive's internal braking chopper or external braking resistor (if installed) to dissipate regenerative energy.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Disconnect the motor from the mechanical load and manually attempt to rotate the shaft to check for binding or excessive friction.

  2. 2

    2. Verify the motor brake functionality by applying a separate 24VDC (or appropriate voltage) to the brake coils and observing full engagement.

  3. 3

    3. Reduce the deceleration time parameter (e.g., P2-11) by 10-20% increments and re-test the emergency ramp function, ensuring the mechanical system can handle it.

  4. 4

    4. Monitor the motor's actual braking current during an emergency stop attempt using parameter P1-02 to ensure it reaches sufficient levels.

  5. 5

    5. Inspect the braking resistor for damage or overheating and measure its resistance value to confirm it is within specified limits.

Ver todos los códigos en este manual (116)