71A5

Mechanical brake opening not allowed

ABB · ACS880

¿Qué significa 71A5 ?

The conditions required for opening the mechanical brake cannot be met, often because the brake is being intentionally kept closed by a parameter setting (e.g., 44.11 Keep brake closed) or due to a safety interlock. This prevents motor operation and is usually a configuration or interlock issue.

Causas comunes

  • Parameter P44-11 (Keep brake closed) is set to 'Always' or 'When stopped', preventing automatic opening.
  • The drive is in a safety state (e.g., STO active) or protective stop that inhibits brake opening.
  • Motor speed (Parameter P01-01) is not zero or below the defined brake release threshold (Parameter P20-03).
  • An external command (e.g., PLC signal via digital input P04-01) is actively holding the brake closed.
  • Internal drive logic or state machine prevents brake opening due to unfulfilled safety or operational conditions.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Check parameter P44-11 (Keep brake closed) setting and ensure it is configured to allow opening as required by the application.

  2. 2

    Verify that no safety function (e.g., STO, Safe Stop 1) is active or preventing drive operation by checking relevant status bits (e.g., P01-14).

  3. 3

    Monitor actual motor speed (Parameter P01-01) and ensure it is below the brake release speed threshold (Parameter P20-03) before attempting to open.

  4. 4

    Check the status of digital inputs (e.g., P04-01 to P04-06) to ensure no external command is holding the brake closed.

  5. 5

    Review the drive's control logic (e.g., using Drive composer's logic viewer) to identify specific conditions preventing brake opening.

Ver todos los códigos en este manual (116)