Charging feedback
ABB · ACS880
¿Qué significa 5697 ?
The feedback signal from the charging system is missing or not detected. This typically indicates a problem with the charging circuit or its monitoring, which could prevent the drive's DC bus from charging correctly, leading to operational failure or preventing the drive from starting.
Causas comunes
- Failure of the pre-charge resistors in the DC bus charging circuit (open circuit).
- Charging contactor or relay in the pre-charge circuit has failed to close its contacts.
- Fault in the DC bus voltage sensing circuit, preventing proper feedback to the control board.
- Failure of the drive's internal auxiliary power supply that energizes the charging control.
- A short circuit on the DC bus (P+, N-) preventing the voltage from rising during pre-charge.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
1. De-energize the drive and wait for the DC bus voltage to discharge completely (monitor P0-01).
- 2
2. Measure the resistance of the pre-charge resistors (e.g., R1, R2) with an ohmmeter; ensure they are not open circuit.
- 3
3. Verify control voltage (e.g., 24VDC) is present and stable on the control board.
- 4
4. Check the operation and continuity of the charging contactor or relay contacts (if external or internal and accessible).
- 5
5. Measure the DC bus voltage across P+ and N- terminals during a restart attempt to observe if voltage begins to rise.