STO input mismatch (_ecSTO_INPUT_MISMATCH)
ABB · ACS850 Standard Program Firmware
¿Qué significa 10035 ?
The drive has detected an inconsistency in its internal Safe Torque Off (STO) registers, meaning the two redundant STO inputs are not in the same state. This is a safety fault that can occur whether the drive is enabled or disabled, indicating a potential failure in the safety circuit or a timing issue, which compromises the STO function.
Causas comunes
- One of the two redundant STO input signals (e.g., STO_IN1, STO_IN2) transitions state (e.g., from 24VDC to 0VDC) significantly before or after the other.
- Asynchronous operation of external safety relays or contacts supplying the two STO inputs, leading to a momentary state difference.
- A wiring fault or intermittent connection on only one of the STO input terminals (e.g., a loose wire at X12.1 but not X12.2).
- Interference (e.g., EMI) affecting only one of the STO input signal lines, causing a momentary false transition.
- Internal timing discrepancy or component tolerance drift within the STO monitoring circuit of the drive.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Using a dual-channel oscilloscope, monitor both STO input signals (e.g., STO_IN1 at X12.1 and STO_IN2 at X12.2) simultaneously to identify any timing discrepancies during state changes.
- 2
Inspect the wiring to both STO input terminals (e.g., X12.1 and X12.2) for any loose connections, damaged insulation, or incorrect termination.
- 3
Test the external safety relays or contactors (e.g., K1, K2) providing the STO signals for consistent and simultaneous opening/closing of their contacts.
- 4
Ensure adequate shielding for the STO input cables, and route them away from power cables or sources of high electromagnetic interference (EMI).
- 5
Confirm that the drive's STO configuration parameters (if any, e.g., P10-01 (STO Delay Time)) are set appropriately for the application and safety component response times.