FF80
DC Bus High Rush
ABB · ACS800 Standard Firmware
¿Qué significa FF80 ?
The drive supply voltage is excessive, exceeding 124% of the unit's nominal voltage rating (e.g., >415V, >500V, or >690V). This overvoltage condition causes the motor speed to rapidly increase, rushing to a trip level of 40% of nominal speed, indicating a potentially dangerous power supply condition.
Causas comunes
- Excessive inrush current detected when powering up the drive.
- Faulty pre-charge resistor or contactor preventing proper inrush current limiting.
- Line voltage fluctuations causing high initial current draw.
- Short circuit on the output stage of the drive.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Measure the incoming AC supply voltage level at the drive input terminals to verify it is within the allowed range.
- 2
Verify the drive's rated voltage matches the actual supply voltage and that the supply voltage falls within the drive's allowed operational voltage range.
Datos técnicos verificados. Última actualización: March 2026