7121
MOTOR STALL
ABB · ACS800 Standard Firmware
¿Qué significa 7121 ?
The motor is operating in a stall region, which occurs when the load exceeds the motor's capability, or the motor power is insufficient for the application. This fault is linked to bit 14 of Fault Word 2 (3.06 FW 2) and controlled by Fault Functions 30.10 through 30.12.
Causas comunes
- Motor speed is zero or near-zero while commanded to run.
- Excessive mechanical load preventing motor rotation.
- Motor winding fault.
- Drive is commanded to run but motor is mechanically blocked.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Evaluate the mechanical load on the motor and compare it against the motor and drive's rated power and torque capabilities.
- 2
Review drive parameters related to motor stall protection, specifically 30.10 (Stall Function), 30.11 (Stall Freq Hi), and 30.12 (Stall Time).
- 3
Adjust the acceleration/deceleration ramps to reduce peak torque demands if the load is dynamic.
Datos técnicos verificados. Última actualización: March 2026