Traduciendo...
A985

External warning 5

ABB · ACS580

¿Qué significa A985 ?

An external device configured as External Event 5 (parameters 31.09 and 31.10) has generated a warning. This indicates a potential issue with external equipment or sensors that should be investigated, though it may not cause an immediate drive trip. Addressing warnings proactively prevents escalation to faults.

Causas comunes

  • Minor leakage detected by a liquid sensor in a pump system, sending a warning signal to the drive's digital input (P31.09, P31.10).
  • Proximity switch on a limit position showing intermittent detection due to mechanical misalignment or debris, generating an oscillating warning.
  • Overload relay on an auxiliary motor tripping momentarily, sending a transient warning signal to the drive.
  • Aging contacts in an external relay or switch, causing an unstable output signal that is interpreted as a warning by the drive.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Identify the external device or process monitoring sensor connected to the digital input specified by P31.09 (External Event 5 source).

  2. 2

    2. Measure the voltage level at the drive's digital input terminal corresponding to the external warning to confirm its state.

  3. 3

    3. Investigate the external equipment or process for the specific condition that would trigger External Event 5 (e.g., fluid levels, mechanical positions, auxiliary motor status).

  4. 4

    4. Confirm P31.09 (External Event 5 source) and P31.10 (External Event 5 action) are correctly configured for the intended external signal and warning response.

  5. 5

    5. Inspect and clean the contacts of any external relays or switches that generate the warning signal, ensuring solid electrical connections.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

ABB A985 (External warning 5) — Biblioteca técnica ErrorLib | ErrorLib